- Transformer accessories

Gas protection relays

The gas protection relay is the most important safety devices for oil-insulated transformers.

Of overheating, corona discharge or arcing

Area of ​​use and material

In the event of overheating, corona discharge or arcing, gas is formed through decomposition of the insulation oil or the solid insulation materials. The gas is then captured in the gas protection relay and initially produces a warning signal. In the event of serious faults or major oil flow, the gas protection relay trips and the transformer is removed from service.

Our gas protection relays have aluminium alloy casings, surface-treated with epoxy lacquer RAL7030. They are equipped with glass inspection windows on both sides. Protection class IP55 with 2 magnetic N/O (normally open) contacts designated -MA. Can be ordered in other configurations (N/C, changeover, etc.) and a test certificate accompanies each gas protection relay.

We have mercury-free replacements for most older gas protection relays; see the table.

ART.NO
TYPE
d1
Substitute prod.
Substitute type
Lenght
Flange diam.
Hole spacing
Num. hole
Drawing
3018 6020-EU026
EU026-MA
25
T0
140
100
75-85
4
3018 6022ET
ET025-MA
25
T1-MA
160
100
75
4
3018 6024
T2-MA
50
185
140
110
4
3018 6025
T3-MA
75
185
190
150
4
3018 6026
T3-TVGC3
75
ASEA
TVGC3
250
190
160
6
3018 6030
BG25-MA
25
Comem/RH
TG1V/H
185
G 1 1/2”
3018 6040
EE1-MA
25
ASEA
TVGB1
127
4 x 76
72
4
3018 6045
EE2-MA
51
ASEA
TVGC2
185
140
110
6
3018 6048
EE3-MA
76
185
160
130
6
3018 6050-S
EB025-MA
25
BR25
200
115
85
4
3018 6055-EB
EB050-MA
50
BR50
195
165
125
4
3018 6058-4-EB
EB079-MA
80
BR80
195
200
160
4
3018 6058-EB
EB080-MA
80
BR80
195
200
160
8

Contact us if you have questions